5-6-7 HP Scroll Series

Split Systems
Systems that are quiet with technology, high with efficiency, friendly with energy…

Profcold ProfessionalCoolingSystems make difference with;
- the minimized design that occupies less places than the similar models,
- quick montage opportunity,
- internal set up chance with its property to work quiet,
- environmental awareness with its low energy use,
- Remote Control and Central Management: The management of the several units locally or online by the software that the system possesses from one point. Delivering the alarms in form of SMS, faxor e-mail to the authorized person (it is optional),
- System Technologies that work with full capacity and provides high efficiency;

 

External Unit

Dimensions : 1060 x 465 x 1400 mm

Sound (MAX): 64 db (A) (1 m'den)

  • Quick montage, simple set up and minimized design.
  • High Efficiency; especially providing more efficieny compared with hermetic compressors in thermal applications.
  • Both work quietly and save energy with the advantage of scroll compressor.
  • Remote Control and Central Management: The management of the several units locally or online by the software that the system possesses from one point. Delivering the alarms in form of SMS, faxor e-mail to the authorized person (it is optional),
5-6-7 HP Scroll Series - External Unit
 
High Efficiency
Comparison of COP ( coefficient of performance ) records according to engine power between scroll and hermetic compressors



 
R 404A - Scroll Compressor

  Cond. Temp. Evaporation Temperature °C
Condenser Unit   °C -50 -45 -40 -35 -30 -25 -20 -15 -10 -5 0 5 7 10 12,5
PSU / 300 TE-HZ Q 30

2,54 3,75 4,75 5,90 7,30 8,90 10,80 12,95 15,40 18,20 19,40 21,40
40

2,02 2,70 4,05 5,10 6,25 7,70 9,30 11,20 13,35 15,80 16,90 18,60
50




3,50 5,20 6,35 7,75 9,35 11,20 13,30 14,20 15,70
5 HP TP 30

2,95 2,97 2,98 2,99 3,00 3,00 2,99 2,97 2,95 2,92 2,90 2,87
40

3,68 3,71 3,73 3,75 3,76 3,76 3,76 3,76 3,74 3,71 3,70 3,68
50




4,65 4,67 4,68 4,68 4,68 4,67 4,65 4,64 4,63
PSU / 400 TE-HZ Q 30

2,95 4,40 5,55 6,69 8,60 10,55 12,75 15,3 18,2 21,5 23 25,30
40

2,35 3,15 4,75 6,00 7,40 9,05 10,95 13,15 15,70 18,60 19,80 21,80
50




4,15 6,15 7,50 9,10 10,95 13,10 15,60 16,6 18,30
6 HP TP 30

3,36 3,4 3,42 3,44 3,43 3,42 3,4 3,38 3,34 3,31 3,3 3,28
40

4,17 4,23 4,28 4,30 4,31 4,31 4,3 4,28 4,24 4,21 4,19 4,16
50














PSU / 400 TE-HZ
Q 30


5,15 6,55 8,20 10,05 12,25 14,80 17,70 21,10 25,00 26,7 29,40
40



5,65 7,05 8,70 10,60 12,75 15,30 18,20 24,50 23,00 25,30
50





5,35 8,85 10,70 12,75 15,20 18,00 19,20 21,20
7 HP
  30


4,20 4,30 4,37 4,41 4,45 4,48 4,53 4,61 4,73 4,80 4,91
40



5,30 5,40 5,50 5,55 5,60 5,65 575 5,75 5,85

50





6,75 8,85 6,90 6,95 6,95 7,00 7,00 7,05
Q(kW)= Capacity
TP(kW)Power Input
10 K Suction Superheat
Working Conditions 20 °C Suction Gas Return
   
Interior Unit
 

Hygiene and Security : CETIM (Hygiene and Security Adaption Certificate ) ( mf ) Rounded corners. the areas which aren’t water retention and simple cleaning. The dropping problem that occurs exterior is minimized.

Minimized Volume : The highness that is minimized to 350 mm and expansion valve which has simple montage.

Simple Access : It can be easily removed for service or cleaning. (all of the components are on upper part of the device.)

Montage and setting : Soft materials , low volumed structure and versatile drenage materials.

Strong structure : Monoblock, anti-shock ABS box.

Performance : Low iner cooling volume.

Low Sound Level : 4 polar engine and polypropylene fan wings.

5-6-7 HP Scroll Series - Interior Unit
 
PLS...Z
PLS...Z













6,35mm
Models PLS...Z

140 195 280 315 415 515 615 635 655 665 775 995
Capacity DT1=8K R404A kw 1,70 2,07 3,17 3,46 4,52 5,49 6,42 6,89 7,41 9,00 10,61 12,20
Ø0m SC 2 (1) Glycol Water kw 1,62
3,33 4,43
6,88





Surface

m2 5,17 7,54 9,33 11,66 15,98 18,64 22,43 27,80 33,7 33,7 28,04 33,65
Working Volume

dm3 1,5 2,3 2,5 3,3 4,4 5,00 6,00 6,9 8,4 8,4 7,5 9

Air Flow
m3/h 1217 1239 2267 2075 2561 3250 3694 3435 3624 4436 7093 7893

Air Flow
m 12 12 12 12 12 12 12 12 12 12 28 45
Fan No x Ømm

1x300 1x300 2x300 2x300 2x300 3x300 3x300 3x300 3x000 4x300 2x400 2x450
1500 r.p.m.

W 145 145 290 290 435 435 435 435 435 580


230 V/1/150 Hz Total A 0,65 0,65 1,30 1,30 1,30 1,95 1,95 1,95 1,95 2,60




W max












400 V/3/50 Hz
A max











No


3 3 3 3 3 3 3 3 3 3 3 3,6

















230 V/1/50 Hz
W 420 630 780 960 1320 1560 1860 2550 3150 3150 2340 1740/3480
Electrical deff 400 V/3/50 Hz Total A 1,8 2,8 3,4 4,2 5,8 6,8 8,1







A






3,7 4,6 4,6 3,4 2,5 / 5,0
Net Weight

Kg
17 19 23 28 33 44 45 58 70 72 65